Тема: MicroSCADA SYS600 v9.1.5
В работе имеется MicroSCADA SYS600 pro v. 9.1.5 с терминалами 5-ой серии. В терминалах REF543 изменены проекты. Соответственно необходимо создать файлы APL library для работы с SYS600. Пользуясь методикой изложенной в документации к CAP 505 (Смотри Приложение 1) создать работающий APL library файл не получается, создаются пустые файлы размером 4 Кбайта. Помогите, пожалуйста, разобраться в ситуации.
Приложение 1.
Uploaded application configurations in REF 54x, REM 54x, REC 52x and RET
54x object types
The REF 54x, REM 54x, REC 52x and RET 54x object types provide an alternative
of using an application configuration, which you can upload from the relay terminal.
Upon completion of the upload, you save the uploaded configuration into the object
type’s user application library. These application configurations are stored without
revision information and are available through the Apl library list, shown in
Fig. 3.9.2.1.-1. The use of uploaded application configurations is outlined below:
1. Insert the device object to the project.
2. Configure the object as explained above, assigning an empty application
configuration. Eventually you will replace it with the uploaded configuration.
Apply the configuration normally and then return to the Project Structure
Navigator.
3. Reopen the General Object Attributes dialog selecting the Communication page
to provide communication settings for the object. Select the communication
protocol and configure the communication settings. Connect the communication
cable, if it has not been done yet.
4. Open the object type’s configuration dialog. Click Apl Utils. and you enter the
dialog for maintaining the user application library.
5. By clicking Receive, the upload starts bringing up a progress indicator dialog.
Upon completion of the upload, you provide the name for the uploaded
configuration. This name will appear in the Apl library list.
6. Close the user application library management dialog by clicking Close. Now,
to assign the newly uploaded application configuration, check the Select New
check box and select the configuration from the Apl library list.
7. Close the object type’s configuration dialog by clicking OK. You are prompted
to confirm the replacement of the application configuration. Click Yes to
enforce the new configuration.